A 35 kVA transformer supplies a load of 12 kW at a power factor of 0.45 lagging.
Find the percentage of full load the transformer is carrying. If additional unity power
factor loads are to be served with the same transformer, how many kW may be added
before the transformer is at full load

  • electrical -

    1. KVA*cosA = 12 KW,
    KVA*0.45 = 12,
    KVA = 26.7. = KVA used.
    %F.L. = (26.7/35) * 100% = 76.3.

    2. P = (35-26.7)cosA,
    P = 8.3*1 = 8.3 KW = Amt of unity P.F.
    Load that can be added.

    Alternate Method:
    1. %F.L. = (12/(35*0.45) * 100% = 76.2

    2. 12KW/0.45 + P/1 = 35 KVA,
    26.7 + P = 35,
    P = 35 - 26.7 = 8.3 KW. = Unity P.F.
    Load that can be added.

Respond to this Question

First Name
School Subject
Your Answer

Similar Questions

  1. physics

    1. x-ray machine operates at 200 kv with a current of 10 mA. The power mus be produced by a transformer which raises the voltage from 220 volts to 200 kilovolts. The power going into and out of the transformer is the same. How much …
  2. Physics

    The generator at a power plant produces AC at 24,000 V. A transformer steps this up to 480,000 V for transmission over power lines. If there are 2,000 turns of wire in the input coil of the transformer, how many turns must there be …
  3. Circuts

    A wye-connected load consists of three impedances of 12+j3 ohms each. The line voltage driving the load is 208V. What is the phase voltage?
  4. Physics

    The generator at a power plant produces AC at 24,000 V. A transformer steps this up to 345,000 V for transmission over power lines. If there are 2,000 turns of wire in the input coil of the transformer, how many turns must there be …
  5. Physics

    Which of the following is correct for a step-down transformer?
  6. Physics

    Suppose there are two transformers between your house and the high-voltage transmission line that distributes the power. In addition, assume your house is the only one using electric power. At a substation the primary of a step-down …
  7. math

    A 300 kVA transformer has a primary winding resistance of 0.4 Ω and a secondary winding resistance of 0.0015 Ω. The iron loss is 2 kW and the primary and secondary voltages are 4 kV and 200 V respectively. If the power factor …
  8. Transformers

    Two 6600/ 250 V transformers have the following short circuited characteristics: Applied voltage 200 V, current 30 A, power input 1200 W for one of the transformers; the corresponding data for other transformer being 120 V, 20 A and …
  9. Physics

    A crane lifts a 200kg load at a steady velocity.It takes 12s to raise the load through 60m. i) What is the power needed to lift the load if there is no friction?
  10. Electrical

    A certain load takes 10kW at 0.5pf lagging when connected to a 230V, 60Hz source. The supply company charges a penalty when the power factor fall below 0.8. What size of capacitor must be used in order to avoid penalty?

More Similar Questions